Application: | Power, Electronic |
---|---|
Phase: | Single |
Core: | Amorphous Alloy Transformer |
Still deciding? Get samples of US$ 3000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Single Phase Pad Mounted Transformer General:
• General: Giantway manufactures a complete line of single phase residential pad mounted distribution transformers in its Giantway Power™ series product line. They are available in standard ratings and configurations or can be customized to meet specific needs.
• Single-phase transformers are available as ANSI I & II transformers (shown above in order). All of these distribution transformers are oil-insulated, selfcooled, available in loop or radial feed, and are dead-front.
• All of these transformers meet or exceed ANSI®, IEEE® and NEMA® standards.
• The ANSI® and IEEE® Type-1frontplate arrangement allows vertical feed to the primary and secondary bushings. It is ideal for single-phase industrial and residential applications where a wide range of kVAs or heavy cabling is required.
• Giantway offers Sourceway Power™ series poly-pads that are usable with most transformers conforming to ANSI® C57.12.25-1990 standard (Type-1 or Type-2).
This polymer pad serves as a shipping pallet as well as an installation pad.
Single Phase Pad Mounts Transformer Specifications:
Design Capacities | |
Primary voltage up to 34.5 kV | Secondary voltage 120/240 V |
Rating power up to 500 kVA | |
Built to customer specifications in accordance with IEEE Std C57.12.00 and DOE | |
Standard | |
Implement ANSI/IEEE C57.12XX; DOE;CSA;IEC | |
Service Conditions | |
Design ambient temperature 0°C or 50°C | |
Design altitude less than 1000m above sea level | |
Types: | |
According to ANSI® C57.12.25-1990 standard: | |
ANSI Type-1 | ANSI Type-2 |
Standard Accessories and Features | |
HV & LV Bushings | Pressure relief device |
nameplate engraved | Drain and filling plug |
Parking Stand | Grounding Bracket and X0 strap |
Bay-o-net & current limiting fuse protection | |
Exterior Finish conforming to ANSI C57.12.28 | |
Optional Accessories and Features | |
Transformers may be provided with the following optional items if specified by the purchaser: | |
An anticorrosion skirt for high contaminated areas | |
Load break switches | Thermometer |
Liquid Level Gauge | High voltage off circuit taps |
Provision for padlocking of load break switches | |
Stud type or spade type low voltage bushings | |
Load break inserts complete with dust cap | |
Exterior Finish conforming to ANSI C57.12.28 | |
Customer stock code and stencilling | |
Bail tabs on the bushing well clamps | |
Provision for a remote fault indicator light | |
Alternative protection devices, specified by the pu rchaser | |
Purchaser specified impedance limits | |
FR3 fire resistant bio degradable insulating fluid LNAN | |
A non resettable device that detects internal transformer faults, incorporates pressure relief,and provides an external indication | |
Permanent and/or temporary bar coding label as shown in ANSI/IEEE C57.12.35 | |
Additional tests may be requested by the purchaser and shall be performed in accordance to ANSI/IEEE C57.12.90 |
Single phase Pad mounted Transformer Parameters | ||||||||
Rating(kVA | High voltage(kV) | No-load Loss | On load Loss | Height(mm) | Depth(mm) | Width(mm) | Oil We ight(kg) | Total Weight(kg) |
15 kVA | 34.5/19.92 13.8/8 13.2/7.6 12.47/7.2 or others |
50 | 195 | 840 | 740 | 610 | 45 | 294 |
25 kVA | 80 | 290 | 840 | 740 | 610 | 68 | 362 | |
37.5 kVA | 106 | 360 | 840 | 760 | 610 | 75 | 476 | |
50 kVA | 135 | 500 | 840 | 810 | 610 | 93 | 553 | |
75 kVA | 190 | 650 | 840 | 860 | 610 | 132 | 672 | |
100 kVA | 280 | 1010 | 910 | 1200 | 965 | 230 | 714 | |
167 kVA | 435 | 1530 | 1000 | 1200 | 965 | 265 | 913 | |
250 kVA | 550 | 2230 | 1250 | 1300 | 1430 | 325 | 1106 |